Quoted standards
JB7115-93 Low-voltage reactive power local compensation device
GB/T15576-2008 General technical condition of low-voltage reactive power compensation device
DL/T597-1996 Technical condition of low-voltage reactive power compensation controller orders
JB/T9663-2013 Low-voltage reactive power automatic compensation controller
Technical parameters
Ambient condition
Altitude: ≤2500m
Working temperature: -25℃~+50℃
Storage temperature: -25℃~+70℃
No Corrosive gas, no conductive dust, no inflammable and explosive media exist, no severe vibration, no snow and rain erosion at stall place
Measuring Data
Measuring voltage: 100V~290V( phase voltage)
Measuring current: 0~5A
Current ratio: 1:1200
Measuring power factor: lagging 0.999~advance 0.999
Working voltage: 380V
Measuring frequency: 45~65Hz
Display active power: 0~6553Kw
Display reactive power: 0~6553 Kvar
Display total harmonic distortion:0.0~100.0%
Input/output signal
Sampling voltage: line voltage 0.4KV
Sampling current: Bus current transformer two times 0~5A
Control output: 12V 30mA/branch(dynamic)
Sampling voltage and sampling current should be same phase
Display functions
LED digital display refresh period≤1s。
Communication interface data
Communication interface: RS-485
protocol:MODBUS Communication protocol
Communication rate: 4800~38400bps(无校验位)
Measuring precision
Voltage: ±0.5% Active power:±1.0%
Current: ±0.5% Reactive power:±1.0%
Power factor:±1.0% Frequency:±0. 1Hz
The above data is based on the controller being opened after 10 minutes, as well as the calibration of 1 years
Reliability
Mean Time Between Failures(MTBF):>25000 hours
It is mostly applied to the inside of outdoor complete set, with GPRS radio signal to collect reactive power factor and active power factor, very easy to operate.